Home page

 




Features

The microprocessor electronic control is made on a standard RACK container with 4 electronic board in EURO standard and connected to the system by means of a pcb and plug connectors on the back side of the container. The four pull-out boards have the following func tions:

¥ POWER board with d.c. stabilized power supply;
¥ MAIN board (CPU) with the microprocessor for the management and the control of the different functions of the regulator and of the timer.
¥ DRIVERS board for the control of the voltage variators motors.
¥ SERVICE board with transformers for the continuous monitoring of the input/output voltage levels.

On the panel of the RACK there are the membrane keypad for the programming of the different functions, the liquid crystal display, the control leds, the main switch, the switch for the manual command of the reduction and the RS232 connector for the remote control.
The internal timer allows the programming of 4 different cycles of reduction during the 24h, is also present a device that automatically by-pass the regulator in case of irregular operation. The RACK is connected to the system by means of pull out connectors to allow the complete removing without disconnecting the screwed connections.

REGULATOR STANDARD PROGRAMMING
It is possible to display all the stored parameters by means of the keypad on the microprocessor electronic control. It is also possible to modify the programming to customize the regulator for all the specific user requirements.

Regulators for installations of public lighting "ELIGHT"
TECHNICAL/FUNCTIONAL CHARACTERISTICS ELETTRONIC CONTROLLER CHARACTERISTICS
Nominal Input voltage 380V+N, Three phases Management Programmable logic microprocessor
Nominal frequency 48/52 Hz Selection 5 function key membrane keypad
Input voltage 350/420V Displaying
2 rows 80 chars LCD display
Type of regulation independent on the three phases R, S, T Communication RS232 serial connector
Nominal output voltage 380V+N, stabilized (3x220V) Communication protocol
MODBUS
Stabilization tolerance +/- 1,5% Installation power on Selection from command external/internal
Load variation from 0 to 100% Reduced rate starting
Selection from command external/internal
Load power factor Any Output voltage controlling by mean of the signals Analogue 4-20mA
Analogue 0-6V
Digital from 1 to 8 levels
Maximum unbalance
between the phases
100% not influence Possibility to display and program Operating parameters
Voltage before the average of the three phases
Voltage after of the three phases
Total harmonic distorsion less than 0,2% Power on lamps voltage
200÷220V Stabilized (programmable)
Efficiency at full load greater than 97% Standard rate voltage 200÷230V Stabilized (programmable)
Operating temperature -20°C ÷ +40°C Reduced rate voltage 165-210V Stabilized (programmable)
Storing temperature -20°C ÷ +75°C Power on cycle duration 0/20 minutes (programmable)
Cooling natural air Falling down cycle duration 0/20 minutes (programmable)
Relative humidity </= 95% Rising cycle duration
0/20 minutes (programmable)
Stabilization Variable auto transformer (variac) Operating daily cycles 4
Transformer BOOSTER Available preset programs 4 To set the parameter accorded to the kind of lamp; To set the parameter according to the different areas of the installation such is urban centre, industrial zones, tourist zones, etc.
Regulator by pass Automatic or manual
Applicable rules EN 60439-1
EN 50081-1
EN 50082-2
Complied directives BT 72/23 CEE e 93/68 CEE
EMC 89/336 CEE, 92/31 CEE e 93/68 CEE
Seasonal setting Enabled or disabled
 

The microprocessor electronic control is made on a standard RACK container with 4 electronic board in EURO standard and connected to the system by means of a pcb and plug connectors on the back side of the container. The four pull-out boards have the following functions:

¥ POWER board with d.c. stabilized power supply;
¥ MAIN board (CPU) with the microprocessor for the management and the control of the different functions of the regulator and of the timer;
¥ DRIVERS board for the control of the voltage variatiors motors;
¥ SERVICE board with transformers for the continuous monitoring of the input/output voltage levels.

On the panel of the RACK there are the membrane keypad for the programming of the different functions, the liquid crystal display, the control leds, the main switch, the switch for the manual command of the reduction and the RS232 connector for the remote control.
The internal timer allows the programming of 4 different cycles of reduction during the 24h, is also present a device that automatically by-pass the regulator in case of irregular operation. The RACK is connected to the system by means of pull-out connectors to allow the complete removing without disconnecting the screwed connections.

REGULATOR STANDARD PROGRAMMING
It is possible to display all the stored parameters by means of the keypad on the microprocessor electronic control. It is also possible to modify the programming to customize the regulator for all the specific user requirements.

The "ELIGHT" flux regulator, besides the standard mode, can have advanced functions in advanced mode "ELIGHT PLUS". In this case the regulator has the possibility to manage the lighting installation with different communication systems: on site using the keypad; or with a remote control (via radio or over the telephone network).
The management in advanced mode of the regulator and of the installation is supported by a measuring devices (multimeter) to sense and measure the following parameters:

• The voltage of the three phases;
• The line current of the three phases ;
• The power factor of the three phases;
• The total apparent power of the three phases;
• The apparent power for each phase;
• The active power of the three phases;
• The active power for each phase;
• The reactive power of the three phases;
• The reactive power for each phase;
• The consumption of total active energy;
• Hours counter of operating in regulation; Hours counter of operating in By-pass.

These parameters besides to be sensed and measured by the devices are also sent to the microprocessor electronic control.
It will use the data in the following ways:
• Displaying of the data on the LCD on the panel;
• Generating alarm thresholds for each single measure;
• Storing the sampling of the data choosing the measures;
• Giving the possibility to display the stored sampling;
• Giving the possibility to read the data using a P.C., remote control.


Regulators for installations of public lighting "ELIGHT PLUS"
TECHNICAL CHARACTERISTICS
Nominal Input voltage
380V+N, Three phases
Nominal frequency 48/52 Hz
Input voltage 350/420V
Type of regulation independent on the three phases R, S, T
Nominal output voltage
380V+N stabilized (3x220V)
Stabilization tolerance +/- 1,5%
Load variation from 0 to 100%
Load power factor any
Maximum unbalance between the phases
100% not influence
Total harmonic distorsion less than 0,2%
Efficiency at full load greater than 97%
Operating temperature -20°C ÷ +40°C
Storing temperature
-20°C ÷ +75°C
Cooling natural air
Relative humidity </=95%
Stabilization Variable auto transformer (variac)
Booster transformer
Regulator by pass
Automatic or manual
Applicable rules EN 60439-1
EN 50081-1
EN 50082-2
Complied directives BT 72/23 CEE e 93/68 CEE
EMC 89/336 CEE, 92/31 CEE e 93/68 CEE
FUNCTIONAL CHARACTERISTICS
Management
Programmable logic microprocessor
Selection 5 function key membrane keypad
Displaying 2 rows 80 chars LCD display
Communication RS232 serial connector
Communication protocol
MODBUS
Installation power on Selection from command external/internal
Reduced rate starting Selection from command external/internal
Output voltage controlling by mean of the signals Analogue 4-20mA
Analogue 0-6V
Digital from 1 to 8 levels
Possibility to Displaying and programming of the operating parameters
Displaying and storing of the following measured values:
• Phase current
• Phase voltage
• Phase power factor
• Total apparent power and phase apparent power
• Total active power and phase active power Counter of consumption of energy
• Hours counter of operating in regulation
• Hours counter of operating in By-pass
• Alarm signalling for out of range values
• RAM storage of the alarms and of the measured values
Power on lamps voltage 200÷220V Stabilized (programmable)
Standard rate voltage 210÷230V Stabilized (programmable)
Reduced rate voltage 165/210V Stabilized (programmable)
Power on cycle duration
0/20 minutes (programmable)
Falling down cycle duration 0/20 minutes (programmable)
Rising cycle duration 0/20 minutes (programmable)
Operating daily cycles 4
Available preset programs 4
To set the parameter accorded to the kind of lamp;
To set the parameter according to the different areas of the installation such is urban centre, industrial zones, tourist zones, etc.
Seasonal setting Enabled or disabled



La ELIT Srl si riserva il diritto di apportare modifiche ai propri prodotti senza preavviso.